OEM Famous Prepayment management solution Companies –Self-Supporting Aluminum Cable– HolleyDetail:
Specifications
DESCRIPTION | Vienība | Novērtēt | Novērtēt | Novērtēt | Novērtēt | Novērtēt | |
1 | Ģenerāldirektors |
| 3×35 + 1×16 + NA25 mm2 | 3×50 + 1×16 + NA35mm2 | 3×70 + 1×16 + NA50 mm2 | 3×25 + 1×16 + NA25 mm2 | 3X120 + 1X16 + NA70 mm2 |
| Manufacturing standard |
| NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 |
2 | DESIGNATION | Caai | Caai | Caai | Caai | Caai | |
| Rated Voltage Uo / U | kV | 0,6 / 1 | 0,6 / 1 | 0,6 / 1 | 0,6 / 1 | 0,6 / 1 |
3 | TERMS OF USE | ||||||
| Maximum temperature in permanent regime. | ° C | 90 | 90 | 90 | 90 | 90 |
| Maximum temperature in overload regime. | ° C | 130 | 130 | 130 | 130 | 130 |
| Maximum temperature in short-circuit mode (5 s) | ° C | 250 | 250 | 250 | 250 | 250 |
4 | CABLES GATHERING: | ||||||
| Maximum wireways, depending on the diameter of thePhase wire | Brīža | 60 | 60 | 60 | 60 | 60 |
5 | PHASE CABLE: | ||||||
| Standarta | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Materiāls | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated Aluminum | |
| Nominal section | mm2 | 35 | 50 | 70 | 25 | 120 |
| Klase | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | Numurs | 7 | 6 | 12 | 6 | 15 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.868 | 0.641 | 0.443 | 1.20 | 0.253 |
| Insulation | ||||||
Materiāls | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | ||
XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
Minimum average thickness | mm | 1.14 | 1.52 | 1.52 | 1.14 | 2.03 | |
Minimum thickness at one point | mm | 1.03 | 1.37 | 1.37 | 1.03 | 1.83 | |
6 | STREET LIGHT CABLE | ||||||
| Standarta | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP 370.250 | |
| Materiāls | Pure Aluminum without Coating | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | |
| Nominal section | mm2 | 16 | 16 | 16 | 16 | 16 |
| Klase | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | Numurs | 7 | 6 | 6 | 6 | 6 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 |
| Insulation | ||||||
| Materiāls | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | |
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | |
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 |
7 | NEUTRAL CABLE SUPPORT | ||||||
Standarti | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | ||
Cable Material | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | ||
Conductivity | % IACS | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | |
Nominal section | mm2 | 25 | 35 | 50 | 25 | 70 | |
Number of wires | 7 | 7 | 7 | 7 | 7 | ||
Wire diameter | mm | 2.13 | 2.52 | 3 023 | 2.13 | 3.57 | |
| Minimum tensile strength | kN | 7.72 | 10.81 | 15.44 | 7.72 | 20.95 |
| Nominal Mass | kg / km | 68.4 | 95.7 | 136.8 | 68.4 | 191.5 |
| Density at 20 ° C | kg / m3 | 2703 | 2703 | 2703 | 2703 | 2703 |
| Electrical resistivity at 20 ° C | Ωmm2 / m | 0.032840 | 0.032840 | 0.032840 | 0.032840 | 0.032840 |
| Maximum electrical resistance in DC at 20 ° C | Ω / km | 1.3511 | 0.9651 | 0.6755 | 1.3511 | 0.4825 |
| Insulation | ||||||
Materiāls | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | Cross-linked polyethylene Xlpe | ||
XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
Minimum average thickness | mm | 1.14 | 1.14 | 1.52 | 1.14 | 1.52 | |
Minimum thickness at one point | mm | 1.03 | 1.03 | 1.37 | 1.03 | 1.37 |
Product detail pictures:

Related Product Guide:
abide by the contract", conforms on the market requirement, joins from the market competition by its good quality likewise as provides more comprehensive and superb support for customers to let them become large winner. The pursue of the company, is definitely the clients' pleasure forOEM Famous Prepayment management solution Companies –Self-Supporting Aluminum Cable– Holley, The product will supply to all over the world, such as: Czech Republic, Accra, Czech Republic, We have a excellent team supplying professional service, prompt reply, timely delivery, excellent quality and best price to our customers. Satisfaction and good credit to every customer is our priority. We are sincerely looking forward to cooperate with customers all over the world. We believe we can satisfy with you. We also warmly welcome customers to visit our company and purchase our products.