China OEM Copper conductor Company –Suspension type Polymeric Insulator – HolleyDetail:
Specifications
| Products Type |
| SUSPENSION TYPE POLYMERIC INSULATOR 13.8 kV | SUSPENSION TYPE POLYMERIC INSULATOR 22.9 kV |
| Funkcijas | Vienība | Novērtēt | Novērtēt |
1 | Operating voltage (Phase – Phase) |
| ≤ 13,8 kV | ≥13.8 kV , ≤22.9 kV |
2 | Designation, model | FXB-24kV/70kN | FXB-36kV/70kN | |
3 | Standarti | IEC 61109:2008, ANSI C29.13 | IEC 61109:2008, ANSI C29.13 | |
4 | Manufacturing Features | |||
Core material | Fiberglass with Fiberglas Round Rod Bar ECR | Fiberglass with Fiberglas Round Rod Bar ECR | ||
Insulated housing and sheds: | High consistency silicone rubber type HTV or LSR | High consistency silicone rubber type HTV or LSR | ||
- Resistance to tracking and erosion of insulating material: Silicone rubber | Class 2A, 6kV (according to ASTM D2303 – IEC 60587) | Class 2A, 6kV (according to ASTM D2303 – IEC 60587) | ||
Material of the coupling hardware | Viltots tērauds | Viltots tērauds | ||
Galvanization of hardware | According to ASTM A153/A153M, average thickness of 86µm | According to ASTM A153/A153M, average thickness of 86µm | ||
Types of coupling | Clevis – Tongue, | Clevis – Tongue | ||
Atslēga | Stainless steel | Stainless steel | ||
5 | Electrical Values: | |||
Operation voltage phase-phase | kV | 10 kV, 13.2 kV to 13.8 kV | 13.8 kV to 22.9 kV | |
Maximum voltage for the insulator Um | kV(R.M.S) | 24 | 36 | |
Nominal frequency | Hz | 60 | 60 | |
Maximum diameter of the insulating part | mm | 98 | 98 | |
Minimum creepage distance | mm | 645 | 945 | |
Minimum arcing distance | mm | 210 | 285 | |
Number of sheds | Numurs | 6 | 9 | |
Sheds diameter | mm | 98 | 98 | |
Passage of the sheds | mm | 35 | 35 | |
Sheds tilt angle | ° | 3 | 3 | |
Withstand voltage at power frequency: | ||||
- Slapjš | kV | ≥100 | ≥110 | |
- Izžūt | kV | ≥130 | ≥140 | |
Impulse withstand voltage 1.2/50us: | kV | |||
- Pozitīvs | kV | ≥190 | ≥240 | |
Low Frequency Test Voltage (RMS to Earth) | kV | 20 | 30 | |
RIV Maximum at 1000 KHz | µv | 10 | 10 | |
6 | Mechanical values: | |||
Specified Maximum Mechanical Load (SML) | kN | 70 | 70 | |
Specified Mechanical Test Load (RTL) | kN | 35 | 35 | |
Griezes moments | N - m | 47 | 47 | |
Serdes diametrs | mm | 16 | 16 | |
Svars | kg | 1.4 | 1.9 | |
7 | Projektēšanas testi | According to clause 10 IEC 61109 | According to clause 10 IEC 61109 | |
8 | Tipa testi | According to clause 11 IEC 61109 | According to clause 11 IEC 61109 | |
9 | Sampling tests | According to clause 12 IEC 61109 | According to clause 12 IEC 61109 | |
10 | Individual tests | According to clause 13 IEC 61109 | According to clause 13 IEC 61109 | |
11 | UV resistance tests | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 |
Product detail pictures:

Related Product Guide:
Our products are broadly regarded and reliable by end users and can meet up with constantly transforming financial and social requires ofChina OEM Copper conductor Company –Suspension type Polymeric Insulator – Holley, The product will supply to all over the world, such as: Salt Lake City, Ukraine, Miami, Our solutions have national accreditation requirements for qualified, good quality items, affordable value, was welcomed by individuals all over the world. Our goods will continue to improve inside the order and appear forward to cooperation with you, Really should any of those items be of interest to you, please letus know. We will be satisfied to provide you a quotation up on receipt of the detailed needs.